SMX12-2A/2 Compact control with safe motion and analog option

2032

New

2 axes with 2 encoder per axis

  • 2x2 sensor inputs for safe motion
    (Incremental, sin / cos, SSI absolute, initiators) and with reference interface for HTL (HD) and resolvers
  • 14 safe digital inputs (8 with OSSD)
  • Secure Digital Out 2 high-side / low-side or high-side 4
  • 2 Signalling outputs
  • 2 pulse outputs
  • 2x2 safe analog input combinations

Dim.(HxDxW): 100x115x112,5 mm
 ATTENTION(s. Fig.)

More details

Delivery: 7-10 Business day

€ 1.098,35 excl. shipping

No products added yet

More info

 

For the interface are 14 safe inputs and 3 shutdown channels in the basic version available which. To max 87 safe I/O can be expanded.

For safe speed and / or position detection are 1-encoder solutions (Inc.- TTL / HTL Sin / COS, Proxi-Sw.) And to a limited extent also 2-encoder solutions (eg.B. Inc. TTL or SSI and Inc.-HTL) supports:

  • Extensive library of pre-configured safety sensors and command devices
  • Full geschwindigkeitsund positional security functions for motion monitoring according to - DIN EN 61800-5-2 integrated into firmware
  • Programmable encoder interface for 2 x Incr-TTL / SIN-COS / SSI front and 1 x HTL or Proxi-SW via terminal connection
  • 4 high-side outputs with 2A
  • Function Block Diagram Oriented Programming
  • included 14 safety inputs, 3 working channels, thereof 1 safe relay output and 2 alarm outputs in the basic unit
  • Short circuit monitoring
  • Multiplying contacts or contact reinforcement by external contactors in conjunction with integrated monitoring possible
  • integrated Extensive diagnostic functions in FW
  • Coded status display on the front side 7-segment display and status LED's
  • Quit / Start / Reset button on the front operated
  • Expandable to max. 87 safe I / O via integrated backplane bus (connector in rail snapped)
  • Optional fieldbus interface (expansion module for ProfiBus / ProfiNet, DeviceNet)

To connect other extension modules to the base module, 2 pcs. of T-bus backplane connectors are necessary.